Beschreibung
1.100% Three-phase unbalanced output,with each phase capable of delivering up to 50% of the rated power
2.Support multiple batteries parallel
3.High voltage battery, Higher efficiency
4.Support storing energy from diesel generator
5. 6 time periods for battery charging/discharging
6.Max.10 PCS parallel for on-grid and off-grid
7.AC coupling to retrofit existing solar system
Model |
TK100G-TPS-EU |
TK200G-TPS-EU |
TK300G-TPS-EU |
TK400G-TPS-EU |
TK500G-TPS-EU |
PV String Input Data |
|
||||
Max. DC Input Power (W) |
13000 |
26000 |
39000 |
52000 |
65000 |
Max. DC Input Voltage (V) |
1000 |
||||
Full Load MPPT Voltage Range (V) |
325-850 |
500-850 |
360-850 |
360-850 |
450-850 |
AC Output Data |
|
||||
PV Input Current (A) |
20+20 |
26+26 |
36+36+36 |
36+36+36+36 |
|
Max AC Output Power (W) |
11000 |
22000 |
33000 |
44000 |
55000 |
Max AC Output Current (A) |
16.5 |
33.0 |
50.2 |
60.9 |
83.6 |
Max. Three-phase Unbalanced Output Current (A) |
22 |
35 |
60 |
70 |
83.3 |
Peak Power (off grid) |
1.5 times of rated power, 10 S |
||||
Generator Input/Smart Load/AC Couple Current (A) |
15.2/40/15.2 |
30.4/80/30.4 |
45.5 / 200 / 45.5 |
60.7 / 200 / 60.7 |
75.8 / 200 / 75.8 |
AC Output Frequency and Voltage |
50/60Hz; 3L/N/PE 220/380Vac, 230/400Vac |
||||
Grid Type |
Three Phase |
||||
Battery Input Data |
|
||||
Battery Type |
Lithium-ion |
||||
Battery Voltage Range (V) |
160-700 |
160-800 |
|||
Max.Charging Current (A) |
37 |
50+50 |
|||
Max.Discharging Current(A) |
37 |
50+50 |
|||
Number of Battery Input |
1 |
2 |
|||
Charging Strategy for Li-Ion Battery |
Self-adaption to BMS |
||||
General Data |
|
||||
Operating Temperature Range (c) |
-40-60°C,>45°C Derating |
||||
Cooling |
Smart Cooling |
||||
Communication with BMS |
CAN |
||||
Monitoring mode |
Wi-Fi+APP |
||||
Protection Degree |
IP65 |